TELEHOUSE TOKYO Tama 3 - Basic information and specifications
Building | Location | Tama, Tokyo |
---|---|---|
No. of available racks | Approx. 1,300 racks | |
Construction | Steel construction with base isolation system | |
Scale | 5 floors above ground | |
Electrical facilities | Power receiving system | 66 kV main/stand-by power system |
In-house power generators | N+1 redundant configuration (continuous 48-hour operation possible with no additional fuel supply) | |
UPS | N+1 redundant configuration (15-minute power supply) | |
Power supply | Max.: Rated 42 kVA (Effective 30 kVA) per rack Avg.: Rated 21 kVA (Effective 15 kVA) per rack Overall: 14 MW |
|
Air conditioning facilities | Air conditioning system | Air-cooled module chillers with underfloor cool air delivery |
Air conditioner configuration | N+2 redundant configuration with UPS | |
Operation and security | Operating framework | Operator on duty 24 hours a day, year-round |
Certification | ISO27001 (ISMS) certified | |
Security | Security gates, biometric authentication, IC cards, security cameras, and tailgating prevention system | |
Amenities | Rest areas, conference rooms, customer operation rooms, nap rooms, shower rooms, and staging rooms |
TELEHOUSE OSAKA 2 - Basic information and specifications
Building | Location | Chuo-ku, Osaka City, Osaka |
---|---|---|
No. of available racks | Approx. 700 racks | |
Construction | Steel construction with base isolation system | |
Scale | 20 floors above ground | |
Electrical facilities | Power receiving system | 77 kV main/stand-by power system |
In-house power generators | N+1 redundant configuration (continuous 48-hour operation possible with no additional fuel supply) | |
UPS | N+1 redundant configuration (15-minute power supply) | |
Power supply | Max.: Rated 30 kVA (Effective 20 kVA) per rack Avg.: Rated 15 kVA (Effective 10 kVA) per rack Overall: 6.6 MW |
|
Air conditioning facilities | Air conditioning system | Air-cooled module chillers with underfloor cool air delivery |
Air conditioner configuration | N+2 redundant configuration with UPS | |
Operation and security | Operating framework | Operator on duty 24 hours a day, year-round |
Certification | ISO 27001 (ISMS) certified | |
Security | Security gates, biometric authentication, IC cards, security cameras, and tailgating prevention system | |
Amenities | Rest areas, conference rooms, customer operation rooms, nap rooms, shower rooms, and staging rooms |